Application of Flame Scanners in Combustion Operations

single burner flame scanner sighting or alignment
Aim flame scanner through the largest cross sectional area of the flame
Courtesy Fireye
Flame detectors or scanners are regularly deployed in combustion applications as a means of confirming the presence of flame in a combustion chamber. The verification that fuel flowing into the utilization equipment is being properly burned and not accumulating unburned in the combustion chamber is the first line of safety in combustion.

Flame scanners use the characteristics of combustion and the electromagnetic emissions from burning fuel to detect flame and distinguish among flames from multiple burners. The instruments rely heavily upon operating principles utilizing visible, infrared, and ultraviolet light measurement and detection.

In single burner applications, simpler sensor and controller combinations can work suitably, but multiple flame applications are candidates for more complex detection devices and controls which can discriminate among multiple flames. Differences in individual flame characteristics, indicated through combustion products, can be utilized to distinguish between flames from different burners. Some photoelectric detectors can distinguish a signature flicker in flames of any type, invisible to the human eye.

Knowledge and understanding of the flame itself, its emissive attributes, and other characteristics are the key to proper flame detection. This may include the temperature of gases within the flame and its specific gas products. Other than temperature, electromagnetic radiation and ionized gas molecules in the flame are commonly used by flame scanners or detectors.

A variety of flame scanners are available for industrial and commercial use, each optimized for particular application sets. Essentially you have a scanner, which acts as a sensor. The signal from the scanner requires amplification and further processing to provide a reliable control signal. Hardware is available as discreet components, allowing a combination of scanner, amplifier, and control units to be combined into a system tailored for specific application requirements. Integrated systems are also available, with all appropriate detection and amplification circuitry built into a single compact unit.

Share your combustion process challenges with application specialists and combine your facility and process knowledge with their product application expertise to develop effective solutions.


Optimizing Boiler Operation - Reduce Standby Cycling

Industrial Boiler
Commercial / Industrial Boiler
Courtesy Victory Energy
Heating of commercial and institutional buildings presents a case where there are energy savings available through the application of an advanced control element able to substantially reduce boiler operation time.

Building owners, boiler engineers, operators and other stakeholders will benefit from this simple and understandable video explanation of some of the inefficiencies associated with boiler operation, and how incorporating an additional control element can minimize boiler dry firing (also called standby cycling). Boiler operation costs can be reduced between 10% and 25%, with a commensurate reduction in carbon footprint, by including the Fireye NXM2G control in the boiler control system.

Watch the video. It's just a few minutes and explains the source of the inefficiency, as well as the solution, in a manner understandable to everyone. More information is available from a combustion product specialist, who can help evaluate the efficiency of your current system or assist with incorporating the latest energy saving features and design into a new installation.

Industrial Burners and Safety Systems - Part Three

CTi Combustion

Igniters

Igniters provide proven ignition energy to immediately light-off the burner. They are permanently installed. Igniters are classified as follows by NFPA:

  • Class 3 special: High energy igniter (HEI) capable of directly igniting the main burner fuel. Generally consists of a spark-rod, and power pack to deliver the high voltage pulse train, and required cabling. Operation time of igniter is no longer than required to light-off burner, within maximum allowed trial-for-ignition time.
  • Class 3: Low capacity igniter applied particularly to gas and oil burners. Ignites the fuel input to the burner under prescribed light-off conditions. The range of class 3 igniters generally do not exceed 4 percent of full load burner input. Operation time of igniter is not longer than required to light-off the burner, within the maximum allowed trial-for-ignition time.
  • Class 2: Medium capability igniter applied particularly to gas and oil burners to ignite the fuel input to the burner under prescribed light-off conditions. The range of class 2 igniters generally is 4 to 10 percent of full-load burner input. Class 2 igniters may remain in operation to support ignition under low-load or adverse operating conditions. Class 2 igniters cannot be used to extend main burner turn-down range.
  • Class 1: High capacity igniter used to ignite the fuel input through the burner. Supports ignition under any burner light-off or operating conditions. Its location and capacity provide sufficient ignition energy at its associated burner to raise any credible combination of burner inputs of both fuel and air above the minimum ignition temperature. Tests are to be performed with this ignition system in service to verify that the igniter furnished meets the requirement of this class as specified in its design. Class 1 igniters can be used to extend the main burner’s turndown, where they are in service and flame if proved.

Industrial Burners and Safety Systems - Part One

Fireye Burner Safety
Fireye Burner Safety Systems
Burners are simple devices that convert fossil fuels into heat energy. In order to achieve safe and reliable operation, each burner must be equipped with a monitoring and control system. The complexity of a safe and reliable system is relative to the complexity of the process at hand. This system can be as simple as a single burner using a single fuel, to a complex multi-burner environment where many burners fire into a common combustion chamber where multiple fuels are burned simultaneously. Conditions affecting the complexity of control systems is not necessarily dependent upon large burner input, but IS dependent upon the following conditions:
  • Type of process. 
  • Type of burner. 
  • Multi- or single burner environment. 
  • Multi or single fuel operation. 
  • Safety hazard of fuel burner. 
  • Local codes and standards. 
  • Redundancy and reliability factors. 
  • Continuous or intermittent burner operation. 
Recent technological advances require knowledge of applications and systems and should be applied only by qualified technicians. Standards are set by local authorities and must be understood and properly operated in order to assure that safety requirements are met.

Flame Discrimination and Detection for Multi-fuel Applications

Safe, reliable infrared and ultraviolet flame discrimination and detection for multi-fuel applications.

Flame scanners are used to detect emissions from fossil fuel flames. These can be gaseous fuel, light petroleum distillates, diesel fuels, heavy fuel oils and a variety of coals. They are suited for application to multiple burner furnaces in utilities and pulp and paper plants, industrial application such as petrochemical, refinery and chemical production, through to industrial boilers. Flame temperature measurement can be used to monitor and report on many applications including specialized burners used in applications such as Low NOx, Incineration and sulfur recovery.