Boiler Combustion Efficiency System Pays Dividends

Industrial Boiler
Industrial Boiler
Steam and hot water use is prevalent throughout industrial processes. Production of these two media is most commonly accomplished with a boiler, many of which are heated by combustion of fossil fuel. Fuel fired boilers of a certain size become the focus of regulatory requirements for emissions. All boilers consume what would be construed by their owners as large amounts of costly fuel. Because of their high pressure and temperature, and the presence of a controlled combustion within an occupied facility, safety is a paramount concern.

There, fortunately, is a single solution that can help to attain useful goals with the three concerns of safety, fuel cost, and regulatory compliance. Applying an efficiency controller to manage the fuel to air ratio of the combustion system will deliver benefits far in excess of the cost to incorporate the necessary devices. The three basic goals for the fuel air controller are:
  • Maximize fuel efficiency
  • Minimize regulated emissions
  • Maintain safe operating condition
A good portion of all three goals can be accomplished through careful concerted parallel control of combustion air supply and fuel supply. The fuel air ratio must be subject to continual adjustment in response to current air conditions (which can vary on a daily basis) and the level of O2 in the flue gas. Controlling the air fuel ratio supports the following goals:
  • Preventing excess fuel vapors from entering the flue and creating an unsafe condition
  • Providing the correct amount of air to effectively combust the fuel supplied to the burner
  • Preventing excess air flow from reducing net heat transfer to the feedwater
  • Maintaining regulated emissions within required limits
  • Limiting fuel consumption to the minimum necessary to meet demand
Fireye® is a leading manufacturer of flame safeguard controls and burner management systems for commercial and industrial applications throughout the world. Their products, the first of which was developed in the 1930's, enhance the safety and efficiency of all fuel fired burners.

There are numerous capabilities built in to the company's PPC4000 series of fuel air ratio controllers. Some of the more notable include:
  • Precise fuel air ratio attained using parallel control of servos to regulate fuel and air supplies.
  • User selected burner profiles
  • Alarm contacts
  • PID operation
  • An array of inputs and outputs to accommodate sensors and devices needed to monitor and control boiler operation
  • Compatible with other products that provide additional flame and burner monitoring safety
  • Multiple boiler sequencing and cold start thermal shock protection
  • On board boiler efficiency calculation
  • User interface, optional larger touchscreen interface
Glance through just the first two pages of the document below to get a full description of the capability of this compact and comprehensive controller. You can get more detailed information, or get a professional evaluation of your current system efficiency, by contacting the combustion experts at CTi Controltech.


Industrial Burners and Safety Systems - Part Three

CTi Combustion

Igniters

Igniters provide proven ignition energy to immediately light-off the burner. They are permanently installed. Igniters are classified as follows by NFPA:

  • Class 3 special: High energy igniter (HEI) capable of directly igniting the main burner fuel. Generally consists of a spark-rod, and power pack to deliver the high voltage pulse train, and required cabling. Operation time of igniter is no longer than required to light-off burner, within maximum allowed trial-for-ignition time.
  • Class 3: Low capacity igniter applied particularly to gas and oil burners. Ignites the fuel input to the burner under prescribed light-off conditions. The range of class 3 igniters generally do not exceed 4 percent of full load burner input. Operation time of igniter is not longer than required to light-off the burner, within the maximum allowed trial-for-ignition time.
  • Class 2: Medium capability igniter applied particularly to gas and oil burners to ignite the fuel input to the burner under prescribed light-off conditions. The range of class 2 igniters generally is 4 to 10 percent of full-load burner input. Class 2 igniters may remain in operation to support ignition under low-load or adverse operating conditions. Class 2 igniters cannot be used to extend main burner turn-down range.
  • Class 1: High capacity igniter used to ignite the fuel input through the burner. Supports ignition under any burner light-off or operating conditions. Its location and capacity provide sufficient ignition energy at its associated burner to raise any credible combination of burner inputs of both fuel and air above the minimum ignition temperature. Tests are to be performed with this ignition system in service to verify that the igniter furnished meets the requirement of this class as specified in its design. Class 1 igniters can be used to extend the main burner’s turndown, where they are in service and flame if proved.

Industrial Burners and Safety Systems - Part Two

Combustion

Industrial Burners and BoilersCombustion (or burning) is a rapid combination of oxygen with fuel, resulting in a release of heat. Air (the oxygen source) is about 21% oxygen and 78% nitrogen by volume. Most fuels contain carbon, hydrogen, and sometimes sulphur. A simplification of combustion could be listed in the following three processes.

carbon + oxygen = carbon dioxide + heat
hydrogen + oxygen = water vapor + heat
sulphur + oxygen = sulphur dioxide + heat

These products of combustion are chemical compounds. They consist of molecules, combined in fixed proportions. Heat given off in any combustion process is excess energy which the molecules must release.

Stoichiometric combustion results when no fuel or air goes unused during the combustion process. Combustion with too much (excess) air is said to be lean or oxidizing. The excess air or oxygen plays no part in the combustion process. In fact, it reduces efficiency. Visually, excess air produces a short and clear flame. Combustion with too much fuel is called rich or reducing, producing incomplete combustion. This flame appears long and some- times smoky. The oxygen supply for combustion generally comes from ambient air.

Industrial Burners and Safety Systems - Part One

Fireye Burner Safety
Fireye Burner Safety Systems
Burners are simple devices that convert fossil fuels into heat energy. In order to achieve safe and reliable operation, each burner must be equipped with a monitoring and control system. The complexity of a safe and reliable system is relative to the complexity of the process at hand. This system can be as simple as a single burner using a single fuel, to a complex multi-burner environment where many burners fire into a common combustion chamber where multiple fuels are burned simultaneously. Conditions affecting the complexity of control systems is not necessarily dependent upon large burner input, but IS dependent upon the following conditions:
  • Type of process. 
  • Type of burner. 
  • Multi- or single burner environment. 
  • Multi or single fuel operation. 
  • Safety hazard of fuel burner. 
  • Local codes and standards. 
  • Redundancy and reliability factors. 
  • Continuous or intermittent burner operation. 
Recent technological advances require knowledge of applications and systems and should be applied only by qualified technicians. Standards are set by local authorities and must be understood and properly operated in order to assure that safety requirements are met.

Flame Discrimination and Detection for Multi-fuel Applications

Safe, reliable infrared and ultraviolet flame discrimination and detection for multi-fuel applications.

Flame scanners are used to detect emissions from fossil fuel flames. These can be gaseous fuel, light petroleum distillates, diesel fuels, heavy fuel oils and a variety of coals. They are suited for application to multiple burner furnaces in utilities and pulp and paper plants, industrial application such as petrochemical, refinery and chemical production, through to industrial boilers. Flame temperature measurement can be used to monitor and report on many applications including specialized burners used in applications such as Low NOx, Incineration and sulfur recovery.

Check out our little promotional video for CTi Combustion. For those who don't know, CTi Combustion specializes in combustion, steam, boilers and burners with engineering expertise in: