Wireless Transmitters In Process Measurement and Control

oil refinery
Industrial process instrumentation connectivity can present
substantial challenges.
In process control, various devices produce signals which represent flow, temperature, pressure, and other measurable elements of the process. In delivering the process value from the measurement point to the point of decision, also known as the controller, systems have traditionally relied on wires. More recently, industrial wireless networks have evolved, though point-to-point wireless systems are still available and in use. A common operating protocol today is known as WirelessHART™ , which features the same hallmarks of control and diagnostics featured in wired systems without any accompanying cables.

Wireless devices and wired devices can co-exist on the same network. The installation costs of wireless networks are decidedly lower than wired networks due to the reduction in labor and materials for the wireless arrangement. Wireless networks are also more efficient than their wired peers in regards to auxiliary measurements, involving measurement of substances at several points. Adding robustness to wireless, self-organizing networks is easy, because when new wireless components are introduced to a network, they can link to the existing network without needing to be reconfigured manually. Gateways can accommodate a large number of devices, allowing a very elastic range for expansion.

In a coal fired plant, plant operators walk a tightrope in monitoring multiple elements of the process. They calibrate limestone feed rates in conjunction with desulfurization systems, using target values determined experientially. A difficult process environment results from elevated slurry temperature, and the associated pH sensors can only last for a limited time under such conditions. Thanks to the expandability of wireless transmitters, the incremental cost is reduced thanks to the flexibility of installing new measurement loops. In regards to maintenance, the status of wireless devices is consistently transmitted alongside the process variable. Fewer manual checks are needed, and preventative measures may be reduced compared to wired networks.

Time Synchronized Mesh Protocol (TSMP) ensures correct timing for individual transmissions, which lets every transmitter’s radio and processor ‘rest’ between either sending or receiving a transmission. To compensate for the lack of a physical wire, in terms of security, wireless networks are equipped with a combination of authentication, encryption, verification, and key management. The amalgamation of these security practices delivers wireless network security equal to that of a wired system. The multilayered approach, anchored by gateway key-management, presents a defense sequence. Thanks to the advancements in modern field networking technology, interference due to noise from other networks has been minimized to the point of being a rare concern. Even with the rarity, fail-safes are included in WirelessHART™.

All security functions are handled by the network autonomously, meaning manual configuration is unnecessary. In addition to process control environments, power plants will typically use two simultaneous wireless networks. Transmitters allow both safety showers and eyewash stations to trigger an alarm at the point of control when activated. Thanks to reduced cost, and their ease of applicability in environments challenging to wired systems, along with their developed performance and security, wireless industrial connectivity will continue to expand.

Share your process measurement requirements and challenges with application specialists, combining your own process knowledge and experience with their product application expertise to develop effective solutions.


CTi Controltech In-House Capabilities and Solutions for Combustion, Automation, and Instrumentation

CTi Controltech has operated in northern California and Nevada for many years, satisfying customers and building their capabilities into today's top flight provider of equipment and services to industrial and commercial markets. The short piece included below is a synopsis of the company's range of products and services.

Share your combustion, emission, steam, process control, and automation challenges with experts in the field. The combination of your own process knowledge with the expertise at CTi Controltech will produce effective solutions.


Control Valve Flow Characteristics

control valve
Valtek ControlValve
Flow characteristics, the relationship between flow coefficient and valve stroke, has been a subject of considerable debate. Many valve types, such as butterfly, eccentric disk and ball valves, have an inherent characteristic which cannot be changed (except with characterizable positioner cams). Flow characteristics of globe valves can be determined by the shape of the plug head.
control valve flow
Control Valve Flow
Characteristics

The three most common types of flow characteristics are quick opening, equal percentage and linear. The adjacent figure shows the ideal characteristic curve for each. These characteristics can be approximated by contouring the plug. However, inasmuch as there are body effects and other uncontrollable factors, plus the need for maximizing the flow capacity for a particular valve, the real curves often deviate considerably from these ideals. When a constant pressure drop is maintained across the valve, the characteristic of the valve alone controls the flow; this characteristic is referred to as the “inherent flow characteristic.” “Installed characteristics” include both the valve and pipeline effects. The difference can best be understood by examining an entire system.

Equal Percentage

Equal percentage is the characteristic most commonly used in process control. The change in flow per unit of valve stroke is directly proportional to the flow occurring just before the change is made. While the flow characteristic of the valve itself may be equal percentage, most control loops will produce an installed characteristic approaching linear when the overall system pressure drop is large relative to that across the valve.

Linear

An inherently linear characteristic produces equal changes in flow per unit of valve stroke regardless of plug position. Linear plugs are used on those systems where the valve pressure drop is a major portion of the total system pressure drop.

Quick Open

Quick open plugs are used for on-off applications designed to produce maximum flow quickly.

This information provided courtesy of Flowserve Valtek. Further technical information can be found at this link.

Measuring Flow - The Basics

flowmeter
Electromagnetic
flowmeter
(courtesy of Azbil)
Flow measurement, the measuring of a flow rate for gasses, liquids and solids,  is used throughout process applications in power generation, chemical manufacturing, petro-chemicals, pulp and paper, water and wastewater, bio-science, semiconductor and many other manufacturing processes. There two primary ways to measure the flow: volumetrically and by weight.

Flowmeters are used to measure the rate of flow (or quantity) of material in an open or closed system. They normally are installed on piping systems with the flow sensor immersed in the process medium.